3. Setup and Connections Vlinx MESR9xx Modbus Gateway
Page 32 Manual Documentation Number MESR9xx-0712m
www.bb-elec.com/
www.bb-europe.com/
a. To access this screen, click the “Next” button or click the “Modbus Priority” link
on the left side of the screen.
b. This screen allows you to configure the gateway to move high priority messages
to the front of the serial message buffer.
Figure 40. Modbus Priority Screen
c. These settings allow the gateway to move high priority messages to the front of
the serial message buffer. The priority can be based on the originating IP address,
the Modbus ID, the Modbus function code, or any combination of the three. Up to
five different priorities can be set.
d. IP Address Used to set a static Internet protocol address for the Modbus
Gateway.
e. Modbus ID Valid range is from 1 to 255.
f. Function Code Valid range is from 1 to 99.
g. Save settings by clicking the “Save” button.